Note that devices used in conjunction with Unitronics controllers must be calibrated according to the available range. Below, Range refers to the value contained by the register that is linked to the I/O in Hardware Configuration.

Analog output values are contained in the register that you link to the output in Hardware Configuration.

Model number

Resolution

Range

V200-18-E1 (Snap-in I/O module)
V120-12-R1, V120-12-R2C

M90 controllers (analog input)

M91-19-R1, M91-19-R2, R2C

10 bit (0-10V, 0-20mA,
4-20mA)
 

0-1023, 1024 units (except at 4-20mA)
204 to 1024, 820 units (at 4-20mA)

V120-12-UN2

M90-19-UN2
M91-19-TC2

14 bit (0-10V, 4-20mA)

Temperature ranges appear in the following table

0-16383, 16384 units (except at 4-20mA)
3277-16383, 13107 units (at 4-20mA)

IO-AI4-AO

Input

 

Output

 

12 bit   (0-10V, 0-20mA,
4-20mA)
 

12 bit +sign (±10V, 0-20mA,
4-20mA)

 

0-4095, 4096 units (except at4-20mA)
819 to 4095, 3277 units (at 4-20mA)

0-+4095(except at4-20mA)
819 to 4095, 3277 units (at 4-20mA)

Model number

Type

Input ranges

Range

V120-12-UN2

M90-19-UN2
M91-19-TC2

mV

B

E

J

K

N

R

S

T

 -5    to 56mV

  200 to 1820° C  (300 to 3276° F)

-200  to 750° C  (-328 to 1382° F)

-200  to 760° C  (-328 to 1400° F)

-200  to 1250° C (-328 to 2282° F)

-200  to 1300° C (-328 to 2372° F)

-0     to 1768° C (-32 to 3214° F)

-0     to 1768° C (-32 to 3214° F)

-200  to 400° C  (-328 to 752° F)

-50    to 506° C

  2000 to 18200° C  (3000 to 32760° F)

-2000  to 7500° C  (-3280 to 13820° F)

-2000  to 7600° C  (-3280 to 14000° F)

-2000  to 12500° C (-3280 to 22820° F)

-2000  to 13000° C (-3280 to 23720° F)

-0     to 17680° C (-32 to 32140F)

-0     to 17680° C (-32 to 32140° F)

-200  to 4000° C  (-3280 to 7520° F
 

IO-PT4

 

-50° to 460°C

-500° to 4600°C

Related Topics

Analog input value--Out Of Range

Hardware Configuration