Note that devices used in conjunction with the controller must be calibrated according to the available range. Below, Range refers to the value contained by the register that is linked to the I/O in Hardware Configuration.
Model number |
Resolution |
Range |
V200-18-E1 (Snap-in I/O module) M90 controllers (analog input) M91-19-R1, M91-19-R2, R2C |
10 bit (0-10V, 0-20mA, |
0-1023, 1024 units (except at 4-20mA) |
V120-12-UN2 M90-19-UN2 |
14 bit (0-10V, 4-20mA)
Temperature ranges appear in the following table |
0-16383, 16384 units (except at 4-20mA) |
IO-AI4-AO2 Input Output |
12 bit (0-10V, 0-20mA, 12 bit +sign ( ±10V, 0-20mA, |
0-4095, 4096 units (except at 4-20mA) |
Model number |
Type |
Input ranges |
Analog Value |
V120-12-UN2 M90-19-UN2 |
mV |
-5 to 56mV |
-500 to 5600 |
Thermocouple type |
|
|
|
B |
200 to 1820° C (300 to 3276° F) |
2000 to 18200 (3000 to 32760) |
|
E |
-200 to 750° C (-328 to 1382° F) |
-2000 to 7500 (-3280 to 13820) |
|
J |
-200 to 760° C (-328 to 1400° F) |
-2000 to 7600 (-3280 to 14000) |
|
K |
-200 to 1250° C (-328 to 2282° F) |
-2000 to 12500 (-3280 to 22820) |
|
N |
-200 to 1300° C (-328 to 2372° F) |
-2000 to 13000 (-3280 to 23720) |
|
R |
-0 to 1768° C (-32 to 3214° F) |
-0 to 17680 (-32 to 32140) |
|
S |
-0 to 1768° C (-32 to 3214° F) |
-0 to 17680 (-32 to 32140) |
|
T |
-200 to 400° C (-328 to 752° F) |
-200 to 4000 (-3280 to 7520) |
|
IO-PT4 |
|
-50° to 460°C |
-500° to 4600°C |